Product description
1 round copper conductor class 1 (6 mm²) or class 2 compacted (>16 mm²) according to DC 4908
2 Insulation of cross-linked polyethylene (XLPE) type DIX 3 according to SR HD 603
3 Outer sheath of PVC type DMV 13 according to SR HD 603, gray color RAL 7001
The cables are intended for the use of electricity in fixed electrical installations.
Reference standard : DC 4141 ENEL
Nominal tension: Uo/U(Um)=0,6/1 (1,2) kV
Minimum temperature of the cable (measured on the sheath):
– during assembly: + 5 °C
– during operation: – 40 °C
The maximum temperature allowed on the phase conductors:
– normal exploitation conditions 90 °C
– during short circuit (max. 5 s) : 250 °C
Minimum radius of curvature: 15 x outer diameter .
Pulling force: max. 5 kgf/mm² of conductor section
Test voltage: 4 kV 50 Hz, 5 min
The cables are flame retarded according to SR EN 60332-1-2
Insulation color: black
- + Construction
1 round copper conductor class 1 (6 mm²) or class 2 compacted (>16 mm²) according to DC 4908
2 Insulation of cross-linked polyethylene (XLPE) type DIX 3 according to SR HD 603
3 Outer sheath of PVC type DMV 13 according to SR HD 603, gray color RAL 7001- + Field of use
The cables are intended for the use of electricity in fixed electrical installations.
- + Technical data
Reference standard : DC 4141 ENEL
Nominal tension: Uo/U(Um)=0,6/1 (1,2) kV
Minimum temperature of the cable (measured on the sheath):– during assembly: + 5 °C
– during operation: – 40 °CThe maximum temperature allowed on the phase conductors:
– normal exploitation conditions 90 °C
– during short circuit (max. 5 s) : 250 °CMinimum radius of curvature: 15 x outer diameter .
Pulling force: max. 5 kgf/mm² of conductor section
Test voltage: 4 kV 50 Hz, 5 min
The cables are flame retarded according to SR EN 60332-1-2
Insulation color: black