U-1000 R02V, U-1000 R12V

Energy cables with cross-linked polyethylene insulation and PVC sheath

Product description

1 Copper conductor class 1 (s≤16 mm²), or class 2 (s≥6 mm²) according to SR EN 60228
2 Cross-linked polyethylene (XLPE) insulation
3 Internal extruded or bandaged covering
4 Outer PVC sheath

The cables are intended for the use of electricity in fixed electrical installations.

Product standard: NF C 32-321
Rated voltage: Uo/U(Um) = 0,6/1 (1,2) kV
Minimum temperature (measured on the cable sheath)

– during assembly: – 5 °C
– during operation: – 40 °C

Maximum temperature allowed on the conductor:

- under normal operating conditions: 90 °C
– during short circuit (max. 5 s): 250 °C

Test voltage: 4 kV 50 Hz, 5 min
The cables have a flame propagation delay (corresponding to the fire test according to SR EN 60332-1-2, category C2 according NF C 32-070)
On request, we produce:

- with increased flame propagation delay (corresponding to the fire test according to SR EN 60332-3-24, similar to category C1 according to NF C 32-070)
– with flexible conductors (class 5)

Isolated conductor identification code: according to SR HD 308

rm – multi-core conductor (class 2)

+ Construction

1 Copper conductor class 1 (s≤16 mm²), or class 2 (s≥6 mm²) according to SR EN 60228
2 Cross-linked polyethylene (XLPE) insulation
3 Internal extruded or bandaged covering
4 Outer PVC sheath

+ Field of use

The cables are intended for the use of electricity in fixed electrical installations.

+ Technical data

Product standard: NF C 32-321
Rated voltage: Uo/U(Um) = 0,6/1 (1,2) kV
Minimum temperature (measured on the cable sheath)

– during assembly: – 5 °C
– during operation: – 40 °C

Maximum temperature allowed on the conductor:

- under normal operating conditions: 90 °C
– during short circuit (max. 5 s): 250 °C

Test voltage: 4 kV 50 Hz, 5 min
The cables have a flame propagation delay (corresponding to the fire test according to SR EN 60332-1-2, category C2 according NF C 32-070)
On request, we produce:

- with increased flame propagation delay (corresponding to the fire test according to SR EN 60332-3-24, similar to category C1 according to NF C 32-070)
– with flexible conductors (class 5)

Isolated conductor identification code: according to SR HD 308

rm – multi-core conductor (class 2)