• Bistrița, Drumul Cetății street, no. 19, Bistrița-Năsăud county

U-1000 AR02V, U-1000 AR12V

Energy cables with cross-linked polyethylene insulation and PVC sheath

Product description

1 Class 1 or class 2 aluminum conductor, according to SR EN 60228
2 Cross-linked polyethylene (XLPE) insulation
3 Internal extruded or bandaged covering
4 Outer PVC sheath

The cables are intended for the use of electricity in fixed electrical installations.

Product standard: NF C 32-321
Rated voltage: Uo/U(Um) = 0,6/1 (1,2) kV
Minimum temperature (measured on the cable sheath)

– during assembly: – 5 °C
– during operation: – 40 °C

Maximum temperature allowed on the conductor:

- under normal operating conditions: 90 °C
– during short circuit (max. 5 s): 250 °C

Test voltage: 4 kV 50 Hz, 5 min
The cables are flame retarded according to SR EN 60332-1-2.
On request, it can also be executed in the version with increased flame propagation delay according to SR EN 60332-3-24.

+ Construction

1 Class 1 or class 2 aluminum conductor, according to SR EN 60228
2 Cross-linked polyethylene (XLPE) insulation
3 Internal extruded or bandaged covering
4 Outer PVC sheath

+ Field of use

The cables are intended for the use of electricity in fixed electrical installations.

+ Technical data

Product standard: NF C 32-321
Rated voltage: Uo/U(Um) = 0,6/1 (1,2) kV
Minimum temperature (measured on the cable sheath)

– during assembly: – 5 °C
– during operation: – 40 °C

Maximum temperature allowed on the conductor:

- under normal operating conditions: 90 °C
– during short circuit (max. 5 s): 250 °C

Test voltage: 4 kV 50 Hz, 5 min
The cables are flame retarded according to SR EN 60332-1-2.