Product description
1 Conductor de aluminiu compactizat, clasa 2 conform SR EN 60228
2 Extruded semiconductor screen.
3 XLPE insulation
4 Extruded semiconductor screen
5 Water-blocking semiconductor tape.
6 Banda de aluminiu cu copolimer, aderenta la mantaua de PE
7 Manta de PE medie densitate, rezistenta la intemperii
Cablurile sunt destinate pentru constructia liniilor electrice de medie tensiune.
Cablurile se pot monta pe estacade, in pamant sau in apa
Product standard: SF 157 IPROEB
Rated voltage:
Uo/U(Um) = 6/10 (12) kV
Uo/U(Um) =12/20 (24) kV
Uo/U(Um) =18/30 (36) kV
Maximum allowable temperature on the conductor
– during normal operation: +90 °C
– during short circuit (max. 5 s): 250 °C
Temperatura minima la instalare: -20 °C
Temperatura minima in exploatare: -40 °C
Tensiuni de incercare :
21 kV, cabluri de 6/10(12) kV
42 kV , cabluri de 12/20(24 kV
63 KV, cabluri de 18/30(36) kV
Nivelul descarcarilor partiale la 1,73Uo: max. 2pC
Minimum radius of curvature: 15 x D
D-diametrul exterior al cablului monopolar
Nota: in cazul unei singure indoiri, de exemplu la intrarea in cofrete, tablouri electrice… este permisa o raza de doua ori mai mica cu conditia ca indoirea sa se faca cu atentie, la temperatura de (10-30) °C sau dupa un sablon.
Pulling strength at screening: max. 30 N/mm² de sectiune conductor
- + Construction
1 Conductor de aluminiu compactizat, clasa 2 conform SR EN 60228
2 Extruded semiconductor screen.
3 XLPE insulation
4 Extruded semiconductor screen
5 Water-blocking semiconductor tape.
6 Banda de aluminiu cu copolimer, aderenta la mantaua de PE
7 Manta de PE medie densitate, rezistenta la intemperii- + Field of use
Cablurile sunt destinate pentru constructia liniilor electrice de medie tensiune.
Cablurile se pot monta pe estacade, in pamant sau in apa- + Technical data
Product standard: SF 157 IPROEB
Rated voltage:Uo/U(Um) = 6/10 (12) kV
Uo/U(Um) =12/20 (24) kV
Uo/U(Um) =18/30 (36) kVMaximum allowable temperature on the conductor
– during normal operation: +90 °C
– during short circuit (max. 5 s): 250 °CTemperatura minima la instalare: -20 °C
Temperatura minima in exploatare: -40 °C
Tensiuni de incercare :21 kV, cabluri de 6/10(12) kV
42 kV , cabluri de 12/20(24 kV
63 KV, cabluri de 18/30(36) kVNivelul descarcarilor partiale la 1,73Uo: max. 2pC
Minimum radius of curvature: 15 x D
D-diametrul exterior al cablului monopolarNota: in cazul unei singure indoiri, de exemplu la intrarea in cofrete, tablouri electrice… este permisa o raza de doua ori mai mica cu conditia ca indoirea sa se faca cu atentie, la temperatura de (10-30) °C sau dupa un sablon.
Pulling strength at screening: max. 30 N/mm² de sectiune conductor