Product description
1 Class 5 flexible copper conductor, according to SR EN 60228
2 R2 quality PVC insulation
In indoor electrical installations.
Technical specification DV 201-ENEL
Rated voltage: UO/U = 450/750 V
Minimum ambient temperature: +5 °C
Ambient temperature during use -40 °C ….. +60 °C
Ambient temperature during transport and storage: -40 °C…+ 70 °C
Allowed temperature on the conductor at short circuit (1 s): 160 °C
Test voltage: 2.5 kV, 50 Hz, 15 min, in water
Minimum radius of curvature: 4D, where D is the outer diameter of the cable.
Maximum pulling strength 50 N/mm² conductor section
Insulated conductors are flame retardant according to SR EN 60332-3-24
The emission of acid halogenated gases according to SR EN 60754-1: max. 22 % (220 mg/g)
- + Construction
1 Class 5 flexible copper conductor, according to SR EN 60228
2 R2 quality PVC insulation
- + Field of use
In indoor electrical installations.
- + Technical data
Technical specification DV 201-ENEL
Rated voltage: UO/U = 450/750 V
Minimum ambient temperature: +5 °C
Ambient temperature during use -40 °C ….. +60 °C
Ambient temperature during transport and storage: -40 °C…+ 70 °C
Allowed temperature on the conductor at short circuit (1 s): 160 °CTest voltage: 2.5 kV, 50 Hz, 15 min, in water
Minimum radius of curvature: 4D, where D is the outer diameter of the cable.
Maximum pulling strength 50 N/mm² conductor section
- + Combustion behavior
Insulated conductors are flame retardant according to SR EN 60332-3-24
The emission of acid halogenated gases according to SR EN 60754-1: max. 22 % (220 mg/g)