• Bistrița, Drumul Cetății street, no. 19, Bistrița-Năsăud county

NA2XS2Y 3.6/6 ; 6/10; 12/20; 18/30 kV

Cabluri de energie de medie tensiune, cu izolatie din polietilena reticulata si manta de polietilena termoplastica, pentru tensiuni nominale Uo/U = 3,6/6; 6/10; 12/20; 18/30 kV

Product description

1 Compacted aluminum conductor, class 2, according to SR EN 60228.
2 Extruded semiconductor screen.
3 XLPE insulation
4 Extruded semiconductor screen
5 Banda semiconductoare (optional)
6 Ecran din sârma de cupru
7 Copper tape
8 Strat separator
9 Manta exterioara de PE

The cables are intended for the distribution of electrical energy in fixed installations, indoors, outdoors, and buried.
The cables have no flame propagation delay.

Standard reference: IEC 60502-2
Product standard: SF 2 IPROEB
Rated voltage:

Uo/U(Um) = 3,6/6 (7,2) kV
Uo/U(Um) = 6/10 (12) kV
Uo/U(Um) = 12/20 (24) kV
Uo/U(Um) = 18/30 (36) kV

Minimum installation temperature of the cable: -20 °C (measured on the sheath)
Maximum allowable temperature on the conductor

– during normal operation: +90 °C
– during short circuit (max. 5 s): 250 °C

Maximum temperature on the conductor under overload conditions:  +130 °C, 8 hours consecutively, but not more than 125 hours/year
Tensiunea de încercare (50Hz, 5 min)

12,5 kV, for the rated voltage 3,6/6 kV
21 kV, for the rated voltage 6/10 kV
42 kV, for the rated voltage 12/20 kV
63 kV, for the rated voltage 18/30 kV

Partial discharge level: max. 2 pC
Minimum bending radius during installation: 15 x exterior diameter

Construction

1 Compacted aluminum conductor, class 2, according to SR EN 60228.
2 Extruded semiconductor screen.
3 XLPE insulation
4 Extruded semiconductor screen
5 Banda semiconductoare (optional)
6 Ecran din sârma de cupru
7 Copper tape
8 Strat separator
9 Manta exterioara de PE

Application

The cables are intended for the distribution of electrical energy in fixed installations, indoors, outdoors, and buried.
The cables have no flame propagation delay.

Technical data

Standard reference: IEC 60502-2
Product standard: SF 2 IPROEB
Rated voltage:

Uo/U(Um) = 3,6/6 (7,2) kV
Uo/U(Um) = 6/10 (12) kV
Uo/U(Um) = 12/20 (24) kV
Uo/U(Um) = 18/30 (36) kV

Minimum installation temperature of the cable: -20 °C (measured on the sheath)
Maximum allowable temperature on the conductor

– during normal operation: +90 °C
– during short circuit (max. 5 s): 250 °C

Maximum temperature on the conductor under overload conditions:  +130 °C, 8 hours consecutively, but not more than 125 hours/year
Tensiunea de încercare (50Hz, 5 min)

12,5 kV, for the rated voltage 3,6/6 kV
21 kV, for the rated voltage 6/10 kV
42 kV, for the rated voltage 12/20 kV
63 kV, for the rated voltage 18/30 kV

Partial discharge level: max. 2 pC
Minimum bending radius during installation: 15 x exterior diameter

en_USEnglish