Product description
1 Conductor de cupru compactizat, clasa 2, conform SR EN 60228
2 Extruded semiconductor screen.
3 XLPE insulation
4 Extruded semiconductor screen
5 Water-blocking semiconductor tape.
6 Copper wire screen
7 Copper strip
8 Banda cu blocare la apa
9 Manta exterioara de PVC
Cablurile sunt destinate pentru distributia energiei electrice în instalatii fixe, în interior, exterior si îngropat
Standard reference: IEC 60502-2
Product standard: SF 2 IPROEB
Rated voltage:
Uo/U(Um) = 3,6/6 (7,2) kV
Uo/U(Um) = 6/10(12) kV
Uo/U(Um) = 12/20(24) kV
Uo/U(Um) = 18/30(36)kV
Minimum installation temperature of the cable: -5 °C (masurata pe manta)
Maximum allowable temperature on the conductor
– during normal operation: +90 °C
– during short circuit (max. 5 s): 250 °C
Maximum temperature on the conductor under overload conditions: +130 °C, 8 hours consecutively, but not more than 125 hours/year
Test voltage (50 Hz, 5 min):
12,5 kV, for the rated voltage 3,6/6 kV
21 kV, for the rated voltage 6/10 kV
42 kV, for the rated voltage 12/20 kV
63 kV, for the rated voltage 18/30 kV
Partial discharge level: max. 2 pC
Minimum bending radius during installation: 15 x exterior diameter
The cables are flame retarded according to SR EN 60332-1-2
- + Construction
1 Conductor de cupru compactizat, clasa 2, conform SR EN 60228
2 Extruded semiconductor screen.
3 XLPE insulation
4 Extruded semiconductor screen
5 Water-blocking semiconductor tape.
6 Copper wire screen
7 Copper strip
8 Banda cu blocare la apa
9 Manta exterioara de PVC- + Field of use
Cablurile sunt destinate pentru distributia energiei electrice în instalatii fixe, în interior, exterior si îngropat
- + Technical data
Standard reference: IEC 60502-2
Product standard: SF 2 IPROEB
Rated voltage:Uo/U(Um) = 3,6/6 (7,2) kV
Uo/U(Um) = 6/10(12) kV
Uo/U(Um) = 12/20(24) kV
Uo/U(Um) = 18/30(36)kVMinimum installation temperature of the cable: -5 °C (masurata pe manta)
Maximum allowable temperature on the conductor– during normal operation: +90 °C
– during short circuit (max. 5 s): 250 °CMaximum temperature on the conductor under overload conditions: +130 °C, 8 hours consecutively, but not more than 125 hours/year
Test voltage (50 Hz, 5 min):12,5 kV, for the rated voltage 3,6/6 kV
21 kV, for the rated voltage 6/10 kV
42 kV, for the rated voltage 12/20 kV
63 kV, for the rated voltage 18/30 kVPartial discharge level: max. 2 pC
Minimum bending radius during installation: 15 x exterior diameter
The cables are flame retarded according to SR EN 60332-1-2