Product description
Construcţie
1 Single-wire copper conductor, class 1 or multi-wire class 2, according to SR EN 60228
2 PVC insulation
Field of use
In protected installations (in pipes, electrical equipment, lighting fixtures, etc.) up to a voltage of 1000 V a.c. or up to 750 V d.c.
Mounting under the plaster, embedded in concrete or under the action of sun rays is not allowed
Technical data
Product standard: SR EN 50525-2-31
Nominal tension: UO/U = 450/750 V
Minimum ambient temperature:
– during assembly: +5 °C
– during operation: -30 °C
Maximum allowable temperature on the conductor during normal operation: +90 °C
Test voltage: 2,5 kV, 50 Hz, 15 min, in water.
Insulated conductors are flame retardant delayed according to SR EN 60332-1-2