• Bistrița, Drumul Cetății street, no. 19, Bistrița-Năsăud county

FY

Conductors with PVC insulation for general use

Product description

1 Single-wire class 1 or multi-wire class 2 copper conductor, according to SR EN 60228
2 PVC insulation

In electrical installations, mounted on/in plaster in pipes for signaling or control circuits.
The conductors for the nominal voltage of 450/750 V can be used in protected installations (in pipes, electrical equipment, lighting fixtures, etc.) up to a voltage of 1000 V a.c. or up to 750 V d.c.
Mounting under plaster, embedded in concrete or under direct sunlight is not allowed.

Standard reference: SR EN 50252-2-31
Product standard: SF 5 IPROEB
Rated voltage:

UO/U= 300/500 V for 0,75 mm2 and 1 mm2
UO/U= 450/750 V for 1,5mm2 up to 400 mm2

Minimum ambient temperature:
– during assembly: +5 °C
– during exploitation: -30 °C
The maximum temperature allowed on the conductor under normal operating conditions: +70 °C
Test voltage:
2 kV, 50 Hz , 15 min, in the water for 0,75 mm2÷1 mm2
2,5 kV, 50 Hz , 15 min, in the water for 1,5 mm2 ÷400 mm2
Insulated conductors are flame retardant according to SR EN 60332-1-2

+ Technical data sheet
+ Construction

1 Single-wire class 1 or multi-wire class 2 copper conductor, according to SR EN 60228
2 PVC insulation

+ Field of use

In electrical installations, mounted on/in plaster in pipes for signaling or control circuits.
The conductors for the nominal voltage of 450/750 V can be used in protected installations (in pipes, electrical equipment, lighting fixtures, etc.) up to a voltage of 1000 V a.c. or up to 750 V d.c.
Mounting under plaster, embedded in concrete or under direct sunlight is not allowed.

+ Technical data

Standard reference: SR EN 50252-2-31
Product standard: SF 5 IPROEB
Rated voltage:

UO/U= 300/500 V for 0,75 mm2 and 1 mm2
UO/U= 450/750 V for 1,5mm2 up to 400 mm2

Minimum ambient temperature:
– during assembly: +5 °C
– during exploitation: -30 °C
The maximum temperature allowed on the conductor under normal operating conditions: +70 °C
Test voltage:
2 kV, 50 Hz , 15 min, in the water for 0,75 mm2÷1 mm2
2,5 kV, 50 Hz , 15 min, in the water for 1,5 mm2 ÷400 mm2
Insulated conductors are flame retardant according to SR EN 60332-1-2

Additional information

Culoare

Albastru, Galben-Verde, Roșu

Secțiune

,

en_USEnglish