Product description
1 Flexible copper conductor, class 5 according to SR EN 60228
2 Elastomeric insulation type G7 according to CEI EN 50363
3 Extruded inner cover
4 External PVC jacket type Rz according to CEI EN 50363
For fixed low-voltage electrical installations, indoors and outdoors.
On walls, metal structures, in channels, tubes or other similar systems.
Can be mounted in the ground.
Reference standard: CEI UNEL 35375
Nominal tension Uo/U = 0,6/1 kV
Maximum temperature allowed on the conductor:
- under normal operating conditions: 90 °C
– during short circuit (max. 5 s) : 250 °C (160 °C if tinned joints)
Test voltage: 4 kV 50 Hz, 5 min
The cables withstand the fire test according to SR EN 60332-3-24.
The amount of gases released while burning according to SR EN 60754-2: max. 22 %
Minimum temperature of the cable (measured on the sheath) at assembly – 5 °C
Minimum radius of bonding: 6 x outer diameter
Maximum pulling force at screening: 50 N/mm²
Static stress force: max. 15 N/mm²
FG7R – monoconductor cables
FG7OR – multiconductor cables
Color code of insulated conductors: according to SR HD 308
- + Construction
1 Flexible copper conductor, class 5 according to SR EN 60228
2 Elastomeric insulation type G7 according to CEI EN 50363
3 Extruded inner cover
4 External PVC jacket type Rz according to CEI EN 50363- + Field of use
For fixed low-voltage electrical installations, indoors and outdoors.
On walls, metal structures, in channels, tubes or other similar systems.
Can be mounted in the ground.- + Technical data
Reference standard: CEI UNEL 35375
Nominal tension Uo/U = 0,6/1 kV
Maximum temperature allowed on the conductor:- under normal operating conditions: 90 °C
– during short circuit (max. 5 s) : 250 °C (160 °C if tinned joints)Test voltage: 4 kV 50 Hz, 5 min
The cables withstand the fire test according to SR EN 60332-3-24.
The amount of gases released while burning according to SR EN 60754-2: max. 22 %
Minimum temperature of the cable (measured on the sheath) at assembly – 5 °C
Minimum radius of bonding: 6 x outer diameter
Maximum pulling force at screening: 50 N/mm²
Static stress force: max. 15 N/mm²FG7R – monoconductor cables
FG7OR – multiconductor cablesColor code of insulated conductors: according to SR HD 308