Product description
1 Conductor de cupru sau aluminiu, unifilar clasa 1 sau multifilar clasa 2, conform SR EN 60228
2 PVC insulation
3 Common coating
4 Manta interioara de PVC
5 Ecran din sârme de aluminiu
6 Strat separator
7 Armatura de benzi de otel zincate (Abz) sau nezincate (Ab)
8 Manta exterioara de PVC
Destinate pentru utilizarea energiei electrice pentru instalatii fixe cu limitarea perturbatiilor electrice fata de cablurile de curenti slabi.
Product standard: ST 6 IPROEB
Rated voltage: U0/U(Um) = 0,6/1 (1,2) kV
Minimum temperature of the cable (measured on the sheath):
– at assembly : +5 °C
– during exploitation: -30 °C
The maximum temperature allowed on the conductor under normal operating conditions: +70 °C
Test voltage: 4 kV, 50 Hz, 5 min
Minimum bending radius during installation: 12 x diametru exterior
Valoarea factorului la 200 mV/m trebuie sa fie maxim 0,7
CYEAlAb(z)Y , ACYEAlAb(z)Y – Cables with flame delay according to SR EN 60332-1-2
CYEAlAb(z)Y-F , ACYEAlAb(z)Y-F – Cabluri cu întârziere marita la propagarea flacarii conform SR EN 60332-3-24.
ru – conductor rotund unifilar
rm – multi-wired round conductor
rmf – la solicitare se pot executa si conductoare de cupru clasa 5
- + Construction
1 Conductor de cupru sau aluminiu, unifilar clasa 1 sau multifilar clasa 2, conform SR EN 60228
2 PVC insulation
3 Common coating
4 Manta interioara de PVC
5 Ecran din sârme de aluminiu
6 Strat separator
7 Armatura de benzi de otel zincate (Abz) sau nezincate (Ab)
8 Manta exterioara de PVC- + Field of use
Destinate pentru utilizarea energiei electrice pentru instalatii fixe cu limitarea perturbatiilor electrice fata de cablurile de curenti slabi.
- + Technical data
Product standard: ST 6 IPROEB
Rated voltage: U0/U(Um) = 0,6/1 (1,2) kV
Minimum temperature of the cable (measured on the sheath):– at assembly : +5 °C
– during exploitation: -30 °CThe maximum temperature allowed on the conductor under normal operating conditions: +70 °C
Test voltage: 4 kV, 50 Hz, 5 min
Minimum bending radius during installation: 12 x diametru exterior
Valoarea factorului la 200 mV/m trebuie sa fie maxim 0,7
CYEAlAb(z)Y , ACYEAlAb(z)Y – Cables with flame delay according to SR EN 60332-1-2
CYEAlAb(z)Y-F , ACYEAlAb(z)Y-F – Cabluri cu întârziere marita la propagarea flacarii conform SR EN 60332-3-24.ru – conductor rotund unifilar
rm – multi-wired round conductor
rmf – la solicitare se pot executa si conductoare de cupru clasa 5