• Bistrița, Drumul Cetății street, no. 19, Bistrița-Năsăud county

CYArY, CYArY-F

Power cables with insulation and PVC sheath reinforced with galvanized steel wires

Product description

1 Class 1 or 2 copper conductor, according to SR EN 60228
2 PVC insulation
3 Common coating
4 Galvanized steel wire reinforcement
5 PVC outer sheath

The cables are intended for the use of electricity in fixed electrical installations, in places with a risk of mechanical damage.

Product standard: SF 9 IPROEB
Standard reference: SR CEI 60502-1
Rated voltage: Uo/U (Um) = 0,6/1 (1,2) kV
Minimum temperature of the cable (measured on the sheath):

– at installation : +5 °C
– during exploitation: -40 °C

The maximum temperature allowed on the conductor under normal operating conditions: +70 °C
Test voltage: 3,5 kV, 50 Hz, 5 min
Minimum bending radius during installation:

15 x cable diameter with one conductor
12 x cable diameter with more conductors

CYArY – Flame retardant cables, according to SR EN 60332-1-2
CYArY-F – Cables with increased flame propagation delay, according to SR EN 60332-3-24
Meaning of conductor symbols:

ru – single-core conductor (class 1)
rm – multi-core conductor (class 2)
sm – multi-core sector conductor (class 2)

+ Construction

1 Class 1 or 2 copper conductor, according to SR EN 60228
2 PVC insulation
3 Common coating
4 Galvanized steel wire reinforcement
5 PVC outer sheath

+ Field of use

The cables are intended for the use of electricity in fixed electrical installations, in places with a risk of mechanical damage.

+ Technical data

Product standard: SF 9 IPROEB
Standard reference: SR CEI 60502-1
Rated voltage: Uo/U (Um) = 0,6/1 (1,2) kV
Minimum temperature of the cable (measured on the sheath):

– at installation : +5 °C
– during exploitation: -40 °C

The maximum temperature allowed on the conductor under normal operating conditions: +70 °C
Test voltage: 3,5 kV, 50 Hz, 5 min
Minimum bending radius during installation:

15 x cable diameter with one conductor
12 x cable diameter with more conductors

CYArY – Flame retardant cables, according to SR EN 60332-1-2
CYArY-F – Cables with increased flame propagation delay, according to SR EN 60332-3-24
Meaning of conductor symbols:

ru – single-core conductor (class 1)
rm – multi-core conductor (class 2)
sm – multi-core sector conductor (class 2)

Additional information

Fire behavior:

With flame delay

en_USEnglish