CSYEcAb(z)Y-F 1 kV rm cl 5

Cables for signaling and automation with PVC insulation and sheath, screened, for rated voltage Uo/U=0,6/1 kV with increased resistance to fire retardant, class 5

Product description

1 Flexible copper conductor class 5, according to EN IEC 60228
2 PVC insulation
3 Inner covering
4 Cu/PET foil screen
5 Inner PVC sheath
6 Reinforcement of galvanized (Abz) or ungalvanized (Ab) steel strips
7 Outdoor PVC sheath, black

In fixed electrical installations, for signaling and automation in d.c. circuits or alternatively in high-voltage stations

Reference standard: SR IEC 60502-1
Rated voltage: Uo/U= 0,6/1 kV
Minimum cable temperature measured on sheath: at laying: + 5 °C, in operation: - 30 °C to +60°C
Maximum admissible conductor temperature: in normal operating conditions: + 70 °C;
Test voltage: 3,5 kV, 50 Hz, 5 min
Minimum bending radius at laying: 8 x outer diameter
Cables are fire retardant, according to
SR EN IEC 60332-3-24 (cat. C). rm-round stranded copper conductor (flexible)

Construction

1 Flexible copper conductor class 5, according to EN IEC 60228
2 PVC insulation
3 Inner covering
4 Cu/PET foil screen
5 Inner PVC sheath
6 Reinforcement of galvanized (Abz) or ungalvanized (Ab) steel strips
7 Outdoor PVC sheath, black

Application

In fixed electrical installations, for signaling and automation in d.c. circuits or alternatively in high-voltage stations

Technical data

Reference standard: SR IEC 60502-1
Rated voltage: Uo/U= 0,6/1 kV
Minimum cable temperature measured on sheath: at laying: + 5 °C, in operation: - 30 °C to +60°C
Maximum admissible conductor temperature: in normal operating conditions: + 70 °C;
Test voltage: 3,5 kV, 50 Hz, 5 min
Minimum bending radius at laying: 8 x outer diameter
Cables are fire retardant, according to
SR EN IEC 60332-3-24 (cat. C). rm-round stranded copper conductor (flexible)