Product description
1 Class 1 or class 2 copper conductor, according to SR EN 60228
2 Mica band
3 Cross-linked polyethylene insulation
4 Tape made of glass fiber fabric
5 Tape made of glass fiber fabric
6 Common Wrap (LSFH)
7 Exterior sheath of thermoplastic polyethylene with reduced emission of smoke and corrosive gases (LSFH), type HM4 according to HD 604
The cables are intended for fixed electrical installations, in public buildings, where life or important material values can be endangered.
When burning, the cables do not release toxic and corrosive gases and have low smoke emission.
Cables can be installed indoors, outdoors, in wet or dry areas.
It is not allowed to install them directly in the ground or in the water.
Product standard: SF 122 IPROEB
Standard reference: DIN VDE 0266
Rated voltage: Uo/U(Um) = 0,6/1 (1,2) kV
Minimum temperature of the cable measured on the sheath:
– at assembly : -5 °C
– during exploitation: -40 °C
Maximum temperature allowed on the conductor:
– during normal operation: +90 °C
– during short circuit (max. 5 s): 250 °C
Test voltage: 4 kV, 50 Hz, 5 min.
Minimum bending radius during installation: 12 x outer diameter
Burning behavior:
The cables have an increased flame propagation delay, according to SR EN 60332-3-24.
The corrosivity of the gases released during combustion, according to SR EN 60754-2:
– pH ≥ 4,3
– conductivity ≤ 100 µS.cm-1
Smoke density according to SR EN 61034: light transmission ≥ 60%
The integrity of the insulation under the direct action of flames: minimum 180 min ( FE 180 ), according to VDE 0472- 814.
Meaning of conductor symbols:
ru – single-wire round conductor (class 1)
rm – multi-wired round conductor (class 2)
- + Construction
1 Class 1 or class 2 copper conductor, according to SR EN 60228
2 Mica band
3 Cross-linked polyethylene insulation
4 Tape made of glass fiber fabric
5 Tape made of glass fiber fabric
6 Common Wrap (LSFH)
7 Exterior sheath of thermoplastic polyethylene with reduced emission of smoke and corrosive gases (LSFH), type HM4 according to HD 604- + Field of use
The cables are intended for fixed electrical installations, in public buildings, where life or important material values can be endangered.
When burning, the cables do not release toxic and corrosive gases and have low smoke emission.
Cables can be installed indoors, outdoors, in wet or dry areas.
It is not allowed to install them directly in the ground or in the water.- + Technical data
Product standard: SF 122 IPROEB
Standard reference: DIN VDE 0266
Rated voltage: Uo/U(Um) = 0,6/1 (1,2) kV
Minimum temperature of the cable measured on the sheath:– at assembly : -5 °C
– during exploitation: -40 °CMaximum temperature allowed on the conductor:
– during normal operation: +90 °C
– during short circuit (max. 5 s): 250 °CTest voltage: 4 kV, 50 Hz, 5 min.
Minimum bending radius during installation: 12 x outer diameter
Burning behavior:
The cables have an increased flame propagation delay, according to SR EN 60332-3-24.
The corrosivity of the gases released during combustion, according to SR EN 60754-2:– pH ≥ 4,3
– conductivity ≤ 100 µS.cm-1Smoke density according to SR EN 61034: light transmission ≥ 60%
The integrity of the insulation under the direct action of flames: minimum 180 min ( FE 180 ), according to VDE 0472- 814.
Meaning of conductor symbols:ru – single-wire round conductor (class 1)
rm – multi-wired round conductor (class 2)