1 Conductor de cupru, clasa 1 sau clasa 2, conform SR EN 60228
2 Cross-linked polyethylene (XLPE) insulation
3 Inner cover
4 Manta exterioară de PVC, tip ST2 conform SR CEI 60502 -1
The cables are intended for the use of electricity in fixed electrical installations
Reference standard: SR CEI 60502-1
Product standard: SF 36 IPROEB
Nominal tension: Uo/U (Um) = 0,6/1 (1,2) kV
Minimum cable temperature (measured on the sheath):
– at assembly : -5 °C
– during exploitation: -40 °C
Maximum temperature allowed on the conductor:
– during normal exploitation conditions: 90 °C
– during short circuit (max. 5 s) : 250 °C
Test voltage: 4 kV, 50 Hz, 5 min
Minimum radius of bonding:
15 x cable diameter with one conductor
12 x cable diameter with more conductors
C2XY – Flame retardant cables, according to SR EN 60332-1-2
C2XY-F – Cables with increased flame propagation delay, according to SR EN 60332-3-24
Meaning of conductor symbols:
ru – single-wire round conductor (class 1)
rm – multi-wired round conductor (class 2)
sm – multi-core sector conductor (class 2)
- + Tab
- + Construction
1 Conductor de cupru, clasa 1 sau clasa 2, conform SR EN 60228
2 Cross-linked polyethylene (XLPE) insulation
3 Inner cover
4 Manta exterioară de PVC, tip ST2 conform SR CEI 60502 -1- + Field of use
The cables are intended for the use of electricity in fixed electrical installations
- + Technical data
Reference standard: SR CEI 60502-1
Product standard: SF 36 IPROEB
Nominal tension: Uo/U (Um) = 0,6/1 (1,2) kV
Minimum cable temperature (measured on the sheath):– at assembly : -5 °C
– during exploitation: -40 °CMaximum temperature allowed on the conductor:
– during normal exploitation conditions: 90 °C
– during short circuit (max. 5 s) : 250 °CTest voltage: 4 kV, 50 Hz, 5 min
Minimum radius of bonding:15 x cable diameter with one conductor
12 x cable diameter with more conductorsC2XY – Flame retardant cables, according to SR EN 60332-1-2
C2XY-F – Cables with increased flame propagation delay, according to SR EN 60332-3-24
Meaning of conductor symbols:ru – single-wire round conductor (class 1)
rm – multi-wired round conductor (class 2)
sm – multi-core sector conductor (class 2)