C2XY, C2XY-F

Cabluri de energie cu izolaţie de polietilenă reticulată şi manta de PVC (similare N2XY conform VDE 0276-603)

The specified products and their possible acceptable variants described in the INSEMEX Notice also comply with the specified requirements regarding the prevention of explosion hazards: SR EN ISO/ IEC 80079-34:2020, SR EN 60079-14:2014/AC:2016. Cables with fire retardant propagation delay are intended for use in fixed electrical installations in zone 1 and zone 2 (group II G – flammable gases, vapors, mists), in compliance with the design, execution, installation and operation conditions for electrical installations in the zone with explosion hazard given by the manufacturer and in accordance with the requirements of SR EN 60079-14.

Product description

Fi;a tehnic[

1 Conductor de cupru, clasa 1 sau clasa 2, conform SR EN 60228
2 Cross-linked polyethylene (XLPE) insulation
3 Inner cover
4 Manta exterioară de PVC, tip ST2 conform SR CEI 60502 -1

The cables are intended for the use of electricity in fixed electrical installations

Reference standard: SR CEI 60502-1
Product standard: SF 36 IPROEB
Nominal tension: Uo/U (Um) = 0,6/1 (1,2) kV
Minimum cable temperature (measured on the sheath):

– at assembly : -5 °C
– during exploitation: -40 °C

Maximum temperature allowed on the conductor:

– during normal exploitation conditions: 90 °C
– during short circuit (max. 5 s) : 250 °C

Test voltage: 4 kV, 50 Hz, 5 min
Minimum radius of bonding:

15 x cable diameter with one conductor
12 x cable diameter with more conductors

C2XY – Flame retardant cables, according to SR EN 60332-1-2
C2XY-F – Cables with increased flame propagation delay, according to SR EN 60332-3-24
Meaning of conductor symbols:

ru – single-wire round conductor (class 1)
rm – multi-wired round conductor (class 2)
sm – multi-core sector conductor (class 2)

+ Tab

Fi;a tehnic[

+ Construction

1 Conductor de cupru, clasa 1 sau clasa 2, conform SR EN 60228
2 Cross-linked polyethylene (XLPE) insulation
3 Inner cover
4 Manta exterioară de PVC, tip ST2 conform SR CEI 60502 -1

+ Field of use

The cables are intended for the use of electricity in fixed electrical installations

+ Technical data

Reference standard: SR CEI 60502-1
Product standard: SF 36 IPROEB
Nominal tension: Uo/U (Um) = 0,6/1 (1,2) kV
Minimum cable temperature (measured on the sheath):

– at assembly : -5 °C
– during exploitation: -40 °C

Maximum temperature allowed on the conductor:

– during normal exploitation conditions: 90 °C
– during short circuit (max. 5 s) : 250 °C

Test voltage: 4 kV, 50 Hz, 5 min
Minimum radius of bonding:

15 x cable diameter with one conductor
12 x cable diameter with more conductors

C2XY – Flame retardant cables, according to SR EN 60332-1-2
C2XY-F – Cables with increased flame propagation delay, according to SR EN 60332-3-24
Meaning of conductor symbols:

ru – single-wire round conductor (class 1)
rm – multi-wired round conductor (class 2)
sm – multi-core sector conductor (class 2)