AUE4*CR, ARE4*CR

Bipolar low voltage cables with aluminum phase conductor and copper concentric neutral, with XLPE insulation and PVC sheath

Product description

1 Single-core round aluminum conductor (10 mm²) or compacted multi-core round aluminum conductor (25 mm²) according to DC 4908
2 Insulation of cross-linked polyethylene (XLPE) type DIX 3 according to SR HD 603
3 Concentric neutral copper wire conductor
4 Separating layer
5 Outer sheath of PVC type DMV 13 according to SR HD 603, gray color RAL 7001

The cables are intended for the use of electricity in fixed electrical installations.

Reference standard : DC 4125 Enel
Nominal tension: Uo/U(Um) = 0,6/1 (1,2) kV
Minimum temperature of the cable (measured on the sheath):

– during assembly: +5 °C
– during operation: – 40 °C

The maximum temperature allowed on the phase conductors:

– normal exploitation conditions 90 °C ;
– during short circuit (max. 5 s) : 250 °C

Bonding radius: 15 x outer diameter
Pulling force: 3 kgf/mm² of phase conductor section
Test voltage: 4 kV 50 Hz, 5 min
The cables are flame retarded according to SR EN 60332-1-2
Insulation color: black

+ Construction

1 Single-core round aluminum conductor (10 mm²) or compacted multi-core round aluminum conductor (25 mm²) according to DC 4908
2 Insulation of cross-linked polyethylene (XLPE) type DIX 3 according to SR HD 603
3 Concentric neutral copper wire conductor
4 Separating layer
5 Outer sheath of PVC type DMV 13 according to SR HD 603, gray color RAL 7001

+ Field of use

The cables are intended for the use of electricity in fixed electrical installations.

+ Technical data

Reference standard : DC 4125 Enel
Nominal tension: Uo/U(Um) = 0,6/1 (1,2) kV
Minimum temperature of the cable (measured on the sheath):

– during assembly: +5 °C
– during operation: – 40 °C

The maximum temperature allowed on the phase conductors:

– normal exploitation conditions 90 °C ;
– during short circuit (max. 5 s) : 250 °C

Bonding radius: 15 x outer diameter
Pulling force: 3 kgf/mm² of phase conductor section
Test voltage: 4 kV 50 Hz, 5 min
The cables are flame retarded according to SR EN 60332-1-2
Insulation color: black