ARE4*R

Low voltage cables with aluminum conductor insulated with XLPE, with PVC sheath

Product description

1 Class 1 round aluminum conductor (S = 10 mm2) or class 2, round compacted (S ≥25 mm2) according to DC 4908 RO
2 Cross-linked polyethylene insulation (XLPE) type DIX 3 according to SR HD 603, black color
3 Outer PVC sheath, type DMV 13 according to SR HD 603, gray color RAL 7001

The cables are intended for the use of electricity in fixed electrical installations.

Reference standard : DC 4152 Enel
Nominal tension: Uo/U(Um) = 0,6/1 (1,2) kV
Minimum temperature of the cable (measured on the sheath):

– during assembly: 5 °C
– during operation: – 40 °C

The maximum temperature allowed on the phase conductors:

– normal exploitation conditions 90 °C
– during short circuit (max. 5 s) : 250 °C

Test voltage: 4 kV 50 Hz, 5 min
Bonding radius: 15 x outer diameter
The cables are flame retarded according to SR EN 60332-1-2

+ Construction

1 Class 1 round aluminum conductor (S = 10 mm2) or class 2, round compacted (S ≥25 mm2) according to DC 4908 RO
2 Cross-linked polyethylene insulation (XLPE) type DIX 3 according to SR HD 603, black color
3 Outer PVC sheath, type DMV 13 according to SR HD 603, gray color RAL 7001

+ Field of use

The cables are intended for the use of electricity in fixed electrical installations.

+ Technical data

Reference standard : DC 4152 Enel
Nominal tension: Uo/U(Um) = 0,6/1 (1,2) kV
Minimum temperature of the cable (measured on the sheath):

– during assembly: 5 °C
– during operation: – 40 °C

The maximum temperature allowed on the phase conductors:

– normal exploitation conditions 90 °C
– during short circuit (max. 5 s) : 250 °C

Test voltage: 4 kV 50 Hz, 5 min
Bonding radius: 15 x outer diameter
The cables are flame retarded according to SR EN 60332-1-2