Product description
1 Conductor purtator de aliaj de aluminiu, rotund multifilar necompactizat
2 Strat separator de folie sintetica (optional)
3 Izolatie de polietilena reticulata (XLPE), culoare gri RAL 7001
4 Conductor de faza de aluminiu, rotund multifilar compactizat, conform SR EN 60228
5 Izolatie de polietilena reticulata (XLPE), culoare neagra
6 Invelis de protectie (manta) de polietilena reticulata (XLPE), culoare gri RAL 7001
Cablurile sunt destinate pentru linii electrice aeriene de distributie a energiei electrice.
Cablurile pot fi instalate pe stalpi, suporti, in tevi si conducte, pe peretii cladirilor
Clasa de reactie la foc : Fca
Reference standard : GSCC009 Enel
Nominal tension: Uo/U (Um) = 0,6/1 (1,2) kV
Minimum temperature of the cable (measured on the sheath):
la montaj: -20 °C
in exploatare: – 40 °C
The maximum temperature allowed on the phase conductors:
in conditii normale de exploatare : 85 °C ;
la scurtcircuit (max. 5 s) : 250 °C
Temperatura maxima admisa pe conductorul neutru purtator :
in conditii normale de exploatare : 65 °C ;
la scurtcircuit (max. 5 s) : 180 °C
Test voltage: 4 kV 50 Hz, 15 min , in apa
Forta maxima pe neutrul purtator: 680 kgf
Raza minimna de curbura: 15 x D,
D-diametru exterior conductor faza (manunchi)
- + Construction
1 Conductor purtator de aliaj de aluminiu, rotund multifilar necompactizat
2 Strat separator de folie sintetica (optional)
3 Izolatie de polietilena reticulata (XLPE), culoare gri RAL 7001
4 Conductor de faza de aluminiu, rotund multifilar compactizat, conform SR EN 60228
5 Izolatie de polietilena reticulata (XLPE), culoare neagra
6 Invelis de protectie (manta) de polietilena reticulata (XLPE), culoare gri RAL 7001- + Field of use
Cablurile sunt destinate pentru linii electrice aeriene de distributie a energiei electrice.
Cablurile pot fi instalate pe stalpi, suporti, in tevi si conducte, pe peretii cladirilor
Clasa de reactie la foc : Fca- + Technical data
Reference standard : GSCC009 Enel
Nominal tension: Uo/U (Um) = 0,6/1 (1,2) kV
Minimum temperature of the cable (measured on the sheath):
la montaj: -20 °C
in exploatare: – 40 °C
The maximum temperature allowed on the phase conductors:
in conditii normale de exploatare : 85 °C ;
la scurtcircuit (max. 5 s) : 250 °C
Temperatura maxima admisa pe conductorul neutru purtator :
in conditii normale de exploatare : 65 °C ;
la scurtcircuit (max. 5 s) : 180 °C
Test voltage: 4 kV 50 Hz, 15 min , in apa
Forta maxima pe neutrul purtator: 680 kgf
Raza minimna de curbura: 15 x D,
D-diametru exterior conductor faza (manunchi)