• Bistrița, Drumul Cetății street, no. 19, Bistrița-Năsăud county

AFY

Aluminum pipes with PVC insulation for fixed electrical installations

Product description

Technical data sheet

1 Single-wire class 1 or multi-wire class 2 aluminum conductor (over 10 mm²) according to SR EN 60228
2 PVC insulation

In fixed indoor electrical installations, mounted in protective tubes.
Mounting under the plaster, embedded in concrete or under the direct action of the sun's rays is not allowed.

Standard reference: STAS 6865/1989
Product standard: SF 145 IPROEB
Rated voltage: up to 750 V
Minimum ambient temperature:
– during assembly: +5 °C
– during exploitation: -30 °C
The maximum temperature allowed on the conductor under normal operating conditions: +70 °C
Test voltage: 2,5 kV, 50 Hz, 15 min, in the water

Insulated conductors are flame retardant according to SR EN 60332-1-2

Technical data sheet

Technical data sheet

Construction

1 Single-wire class 1 or multi-wire class 2 aluminum conductor (over 10 mm²) according to SR EN 60228
2 PVC insulation

Application

In fixed indoor electrical installations, mounted in protective tubes.
Mounting under the plaster, embedded in concrete or under the direct action of the sun's rays is not allowed.

Technical data

Standard reference: STAS 6865/1989
Product standard: SF 145 IPROEB
Rated voltage: up to 750 V
Minimum ambient temperature:
– during assembly: +5 °C
– during exploitation: -30 °C
The maximum temperature allowed on the conductor under normal operating conditions: +70 °C
Test voltage: 2,5 kV, 50 Hz, 15 min, in the water

Insulated conductors are flame retardant according to SR EN 60332-1-2