Product description
1 Class 1 or class 2 aluminum conductor, according to SR EN 60228
2 Cross-linked polyethylene (XLPE) insulation
3 Aluminum wire reinforcement
4 Outer sheath of PVC type ST2 according to SR CEI 60502-1
The cables are intended for the use of electricity in fixed electrical installations, in alternating current or direct current.
Product standard: SF 36 IPROEB
Reference standard: SR CEI 60502-1
Nominal tension: Uo/U = 0,6/1 kV
Minimum admissible temperature on the sheath
– at assembly : -5 °C
– during exploitation: -40 °C
Maximum temperature allowed on the conductor:
– during normal exploitation: +90 °C
– during short circuit (max. 5 s): 250 °C
Test voltage: 4 kV, 50 Hz, 5 min
Bonding radius: 15 x outer diameter
AC2XAlY : fire retardant delayed cable according to SR EN 60332-1-2.
AC2XAlY-F: increased flame retardant delayed cable according to SR EN 60332-3-24.
Meaning of conductor symbols:
ru – single-wire round conductor (class 1)
rm – multi-wired round conductor (class 2)
- + Construction
1 Class 1 or class 2 aluminum conductor, according to SR EN 60228
2 Cross-linked polyethylene (XLPE) insulation
3 Aluminum wire reinforcement
4 Outer sheath of PVC type ST2 according to SR CEI 60502-1- + Field of use
The cables are intended for the use of electricity in fixed electrical installations, in alternating current or direct current.
- + Technical data
Product standard: SF 36 IPROEB
Reference standard: SR CEI 60502-1
Nominal tension: Uo/U = 0,6/1 kV
Minimum admissible temperature on the sheath– at assembly : -5 °C
– during exploitation: -40 °CMaximum temperature allowed on the conductor:
– during normal exploitation: +90 °C
– during short circuit (max. 5 s): 250 °CTest voltage: 4 kV, 50 Hz, 5 min
Bonding radius: 15 x outer diameter
AC2XAlY : fire retardant delayed cable according to SR EN 60332-1-2.
AC2XAlY-F: increased flame retardant delayed cable according to SR EN 60332-3-24.
Meaning of conductor symbols:ru – single-wire round conductor (class 1)
rm – multi-wired round conductor (class 2)