AC2XAbY, AC2XAbY-F, AC2XAbzY, AC2XAbzY-F

Power cables with cross-linked polyethylene insulation and PVC sheath, with steel strip reinforcement

The specified products and their possible acceptable variants described in the INSEMEX Notice also comply with the specified requirements regarding the prevention of explosion hazards: SR EN ISO/ IEC 80079-34:2020, SR EN 60079-14:2014/AC:2016.

Cables with fire retardant propagation delay are intended for use in fixed electrical installations in zone 1 and zone 2 (group II G – flammable gases, vapors, mists), in compliance with the design, execution, installation and operation conditions for electrical installations in the zone with explosion hazard given by the manufacturer and in accordance with the requirements of SR EN 60079-14. 

Product description

1 Class 1 or class 2 aluminum conductor, according to SR EN 60228
2 Cross-linked polyethylene (XLPE) insulation
3 Extruded or bandaged inner cover
4 Galvanized (Abz) or ungalvanized (Ab) steel strip reinforcement
5 PVC outer sheath

The cables are intended for the use of electricity in fixed electrical installations.
Single-conductor cables are not intended for use in alternating current

Product standard: SF 36 IPROEB
Reference standard: SR CEI 60502-1
Nominal tension: Uo/U = 0,6/1 kV
Minimum admissible temperature on the sheath
– at assembly : -5 °C
– during exploitation: -40 °C
Maximum temperature allowed on the conductor:

– during normal exploitation: +90 °C
– during short circuit (max. 5 s): 250 °C

Test voltage: 4 kV, 50 Hz, 5 min
Bonding radius:

– 15 x outer diameter: cables with one conductor
– 12 x outer diameter: multiconductor cables.

AC2XAb(z)Y : fire retardant delayed cable according to SR EN 60332-1-2.
AC2XAb(z)Y-F: increased flame retardant delayed cable according to SR EN 60332-3-24
Meaning of conductor symbols:

ru – single-wire round conductor (class 1)
rm – multi-wired round conductor (class 2)
su – single-core sector conductor (class 1)
sm – multi-core sector conductor (class 2)

+ Technical data sheet
+ Construction

1 Class 1 or class 2 aluminum conductor, according to SR EN 60228
2 Cross-linked polyethylene (XLPE) insulation
3 Extruded or bandaged inner cover
4 Galvanized (Abz) or ungalvanized (Ab) steel strip reinforcement
5 PVC outer sheath

+ Field of use

The cables are intended for the use of electricity in fixed electrical installations.
Single-conductor cables are not intended for use in alternating current

+ Technical data

Product standard: SF 36 IPROEB
Reference standard: SR CEI 60502-1
Nominal tension: Uo/U = 0,6/1 kV
Minimum admissible temperature on the sheath
– at assembly : -5 °C
– during exploitation: -40 °C
Maximum temperature allowed on the conductor:

– during normal exploitation: +90 °C
– during short circuit (max. 5 s): 250 °C

Test voltage: 4 kV, 50 Hz, 5 min
Bonding radius:

– 15 x outer diameter: cables with one conductor
– 12 x outer diameter: multiconductor cables.

AC2XAb(z)Y : fire retardant delayed cable according to SR EN 60332-1-2.
AC2XAb(z)Y-F: increased flame retardant delayed cable according to SR EN 60332-3-24
Meaning of conductor symbols:

ru – single-wire round conductor (class 1)
rm – multi-wired round conductor (class 2)
su – single-core sector conductor (class 1)
sm – multi-core sector conductor (class 2)