Product description
1 Compacted copper or aluminum conductor, class 2, according to SR EN 60228
2 Extruded semiconductor screen.
3 XLPE insulation
4 Extruded semiconductor screen
5 Semiconductor strip
6 Copper strip screen
7 Internal coating
8 Inner PVC sheath
9 Galvanized (Abz) or ungalvanized (Ab) steel strip reinforcement
10 PVC outer sheath
The cables are intended for the distribution of electricity in fixed installations, for the nominal voltage Uo/U= 3.6/6 kV and Um = 7.2 kV, at 50 Hz.
The cables are intended for laying in the ground, channels, tubes, outdoors.
Product standard: SF 96 IPROEB
Standard reference: IEC 60502-2
Rated voltage: Uo/U(Um) = 3,6/6 (7,2) kV
Minimum temperature of the cable (measured on the sheath):
– at assembly : -5 °C
– during exploitation: -40 °C
Maximum allowable temperature on the conductor
– during normal operation: +90 °C
– during short circuit (max. 5 s): 250 °C
Maximum temperature on the conductor under overload conditions: +130 °C, 8 hours consecutively, but not more than 125 hours/year
Test voltage: 12,5 kV, 50 Hz, 5 min
Partial discharge level: max. 2 pC
Minimum bending radius during installation: 15 x exterior diameter
The cables are flame retarded according to SR EN 60332-1-2
Cables which have F la sfarsitul simbolului sunt cu intarziere marita la propagarea flacarii conform SR EN 60332-3-24
- + Construction
1 Compacted copper or aluminum conductor, class 2, according to SR EN 60228
2 Extruded semiconductor screen.
3 XLPE insulation
4 Extruded semiconductor screen
5 Semiconductor strip
6 Copper strip screen
7 Internal coating
8 Inner PVC sheath
9 Galvanized (Abz) or ungalvanized (Ab) steel strip reinforcement
10 PVC outer sheath- + Field of use
The cables are intended for the distribution of electricity in fixed installations, for the nominal voltage Uo/U= 3.6/6 kV and Um = 7.2 kV, at 50 Hz.
The cables are intended for laying in the ground, channels, tubes, outdoors.- + Technical data
Product standard: SF 96 IPROEB
Standard reference: IEC 60502-2
Rated voltage: Uo/U(Um) = 3,6/6 (7,2) kV
Minimum temperature of the cable (measured on the sheath):– at assembly : -5 °C
– during exploitation: -40 °CMaximum allowable temperature on the conductor
– during normal operation: +90 °C
– during short circuit (max. 5 s): 250 °CMaximum temperature on the conductor under overload conditions: +130 °C, 8 hours consecutively, but not more than 125 hours/year
Test voltage: 12,5 kV, 50 Hz, 5 min
Partial discharge level: max. 2 pC
Minimum bending radius during installation: 15 x exterior diameter
The cables are flame retarded according to SR EN 60332-1-2
Cables which have F la sfarsitul simbolului sunt cu intarziere marita la propagarea flacarii conform SR EN 60332-3-24